ACSR Pelican Conductor size 477.0
ACSR Pelican Conductor Stranding 18/1
ACSR Pelican Conductor weight per km 770.9 kg/km
ACSR Pelican Conductor overall diameter 20.7 mm
ACSR Pelican Conductor current carrying capacity 646 Amps
ACSR Pelican Conductor resistance and reactance

Learn more about ACSR Conductor

Applications

ACSR Pelican Conductor is suitable for use in all practical spans on wood poles, transmission towers, and other structures. Applications range from long, extra high voltage (EHV) transmission lines to sub-service spans at distribution or utilization voltages on private premises.

ACSR (aluminum conductor steel reinforced) has a long service record because of its economy, dependability, and strength to weight ratio. The combined light weight and high conductivity of aluminum with strength of the steel core enables higher tensions, less sag, and longer spans than any alternative.

Also Known As:

477.0 Pelican steel reinforced cable, 477.0 Pelican acsr wire, 477.0 Pelican acsr cable, 477.0 Pelican aluminum conductor steel reinforced, 477.0 Pelican acsr aluminum conductor steel reinforced, 477.0 Pelican all aluminum conductor, 477.0 Pelican aluminum alloy cable, 477.0 Pelican abrasive resistant cable, 477.0 Pelican transmission overhead, 477.0 Pelican overhead power line components.

Standards:

B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
B-231 Aluminum Conductors, Concentric-Lay-Stranded
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-502 Aluminum-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AW)
B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR)
B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)

ACSR Pelican Conductor Specification

Get all the answers to the most frequently asked questions (FAQs) regarding ACSR Pelican Conductor Specifications,ACSR Pelican Conductor data sheet,ACSR Pelican Conductor size,ACSR Pelican Conductor full form,ACSR Pelican Conductor ampacity,ACSR Pelican Conductor diameter and much, much more technical specification.

Code Name Pelican
Size AWG 477.0
Stranding (AL/STL) 18/1
Diameter Individual Wire Aluminum 0.1628 Inches
Diameter Individual Wire Steel 0.1628 Inches
Diameter Steel Core 0.1628 Inches
Diameter Complete Cable (O.D.) 0.814 Inches
Weight (lb/1000 ft) AL 447.8 Lbs
Weight (lb/1000 ft) STL 70.2 Lbs
Weight (lb/1000 ft) TOTAL 518 Lbs
Content - Al 86.45 %
Content - Stl 13.55 %
Rated Breaking Strength 11800 Lbs
Resistance DC 20 ºC Per MFT (ohm) 0.0360 Ω
Resistance AC 75 ºC per MFT (ohm) 0.0442 Ω
Rating 646 Amps
Standard Package Length (Feet) 4015 ft.8030 ft.
Standard Package Weight (Lbs.) 2080 Lbs4160 Lbs
Reel Size NR 48.28 NR 66.28 RM 66.32 NR STL 71.48

*Data provided on this page is subject to change based on different manufacturers variances.

ACSR Pelican Conductor Price

The price of ACSR Pelican Conductor is influenced by various factors such as the market prices of aluminum and steel, manufacturing costs, transportation costs, supply and demand in the market. If you need to get the ACSR Pelican Conductor price per kg, you can directly contact us by email or whatsapp. As a manufacturer of ACSR Pelican Conductor, we will quote a very low price that meets your expectations according to the specifications, length and quantity you need .

Whatsapp Chat Email to us

As a professional ACSR Pelican Conductor manufacturer, JYTOP has over 30 years of production experience and 15 years of export experience.Our acsr dog conductor export such as South Africa, Philippines, Indonesia, Malaysia, Singapore, Vietnam, Korea, Mongolia, Yemen, Cambodia, Thailand, Kenya, Tanzania, UAE, Botswana,Nigeria, Panama, Iran etc.High quality service and production are the first choice of many customers.

HS Code for ACSR Pelican Conductor

The HS code for ACSR Pelican Conductor is 7614100000.
HSN code for ACSR Pelican Conductor in India is 7614100000.

*The HS code is used for customs and trade purposes to identify products and determine duties and taxes on imports and exports.

Following ACSR Conductor Types We Offer:

If you have any questions regarding our services, please contact us or email at [email protected].

Related Products:

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

Request a quote