Bobolink/ACSS/TW Conductor

ACSS/TW Conductor

1431 Bobolink/ACSS/TW Aluminum Conductor Steel Supported Trapezoidal Shaped Aluminum Strands

Get Latest Price Email to us

Item Value
Bobolink/ACSS/TW Conductor size 1431
Bobolink/ACSS/TW Conductor Stranding 36/7
Bobolink/ACSS/TW Conductor weight per km 2,397.4 kg/km
Bobolink/ACSS/TW Conductor overall diameter 32.8 mm
Bobolink/ACSS/TW Conductor current carrying capacity @75 °C:1243amps
@100 °C:1538amps
@150 °C:1958amps
@200 °C:2276amps
@250 °C:2549 Amps
Bobolink/ACSS/TW Conductor resistance and reactance

Learn more about ACSS ACSS/AW ACSS/TW Conductor

Applications

Bobolink/ACSS/TW Conductor is designed for overhead distribution and transmission lines. ACSS/TW is designed to operate continuously at elevated temperatures up to 250°C without loss of strength, it sags less under emergency electrical loadings than ACSR/TW, excellent self-damping properties, and its final sags are not affected by long-term creep of aluminum.

Also Known As:

Bobolink/ACSS/TW Conductor,Bobolink/ACSS/TW Cable,Bobolink/ACSS/TW Wire,1431 Bobolink/ACSS/TW Conductor,1431 Bobolink/ACSS/TW Cable,1431 Bobolink/ACSS/TW Wire.

Standards:

B500 Metallic Coated Stranded Steel Core for Use in Overhead Electrical Conductors.
B502/B502M (optional) Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors
B609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
B802 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
B803 High-Strength Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors.
B856 Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS).
B958 Extra-High-Strength and Ultra-High-Strength Class A Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors.

Bobolink/ACSS/TW Conductor Specification

Get all the answers to the most frequently asked questions (FAQs) regarding Bobolink/ACSS/TW Conductor Specifications,Bobolink/ACSS/TW Conductor data sheet,Bobolink/ACSS/TW Conductor size,Bobolink/ACSS/TW Conductor full form,Bobolink/ACSS/TW Conductor ampacity,Bobolink/ACSS/TW Conductor diameter and much, much more technical specification.

Size (kcmil)1431
Type No.7
Cross Sectional Area Aluminum (in²)1.1236
Cross Sectional Area Total (in²)1.2017
Stranding No of Layers of Aluminum3
Stranding No. of Aluminum Wires36
No. & Diameter Individual Steel Wire7 x 0.1189
Diameter Steel Core (in.)0.3567
Diameter Complete Cable (in.)1.291
Alum. Weight (lbs/MFT)1347
Steel Weight (lbs/MFT)263.1
Total Weight (lbs/MFT)1611
Rated Breaking Strength Standard Strength (lbs)25,100
Rated Breaking Strength High Strength (lbs)27,000
Rated Breaking Strength Ultra High Strength (lbs)30,500
Resistance DC @ 20 °C (ohms/mile)0.0617
Resistance AC @ 75 °C (ohms/mile)0.0802
Ampacity @ 75 °C (amps)1243
Ampacity @ 100 °C (amps)1538
Ampacity @ 150 °C (amps)1958
Ampacity @ 200 °C (amps)2276
Ampacity @ 250 °C (amps)2549

*Data provided on this page is subject to change based on different manufacturers variances.

Bobolink/ACSS/TW Conductor Price

The price of Bobolink/ACSS/TW Conductor is influenced by various factors such as the market prices of aluminum and steel, manufacturing costs, transportation costs, supply and demand in the market. If you need to get the Bobolink/ACSS/TW Conductor price per kg, you can directly contact us by email or whatsapp. As a manufacturer of Bobolink/ACSS/TW Conductor, we will quote a very low price that meets your expectations according to the specifications, length and quantity you need .

Whatsapp Chat Email to us

As a professional Bobolink/ACSS/TW Conductor manufacturer, JYTOP has over 30 years of production experience and 15 years of export experience.Our acsr dog conductor export such as South Africa, Philippines, Indonesia, Malaysia, Singapore, Vietnam, Korea, Mongolia, Yemen, Cambodia, Thailand, Kenya, Tanzania, UAE, Botswana,Nigeria, Panama, Iran etc.High quality service and production are the first choice of many customers.

HS Code for Bobolink/ACSS/TW Conductor

The HS code for Bobolink/ACSS/TW Conductor is 7614100000.
HSN code for Bobolink/ACSS/TW Conductor in India is 7614100000.

*The HS code is used for customs and trade purposes to identify products and determine duties and taxes on imports and exports.

Following ACSS Conductor Types We Offer:

If you have any questions regarding our services, please contact us or email at [email protected].

Related Products:

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

Request a quote