Platte/ACSS/TW Conductor

ACSS/TW Conductor

1569 Platte/ACSS/TW Aluminum Conductor Steel Supported Trapezoidal Shaped Aluminum Strands

Get Latest Price Email to us

Item Value
Platte/ACSS/TW Conductor size 1569
Platte/ACSS/TW Conductor Stranding 33/7
Platte/ACSS/TW Conductor weight per km 2,519.5 kg/km
Platte/ACSS/TW Conductor overall diameter 33.9 mm
Platte/ACSS/TW Conductor current carrying capacity @75 °C:1319amps
@100 °C:1637amps
@150 °C:2092amps
@200 °C:2439amps
@250 °C:2692 Amps
Platte/ACSS/TW Conductor resistance and reactance

Learn more about ACSS ACSS/AW ACSS/TW Conductor

Applications

Platte/ACSS/TW Conductor is designed for overhead distribution and transmission lines. ACSS/TW is designed to operate continuously at elevated temperatures up to 250°C without loss of strength, it sags less under emergency electrical loadings than ACSR/TW, excellent self-damping properties, and its final sags are not affected by long-term creep of aluminum.

Also Known As:

Platte/ACSS/TW Conductor,Platte/ACSS/TW Cable,Platte/ACSS/TW Wire,1569 Platte/ACSS/TW Conductor,1569 Platte/ACSS/TW Cable,1569 Platte/ACSS/TW Wire.

Standards:

B500 Metallic Coated Stranded Steel Core for Use in Overhead Electrical Conductors.
B502/B502M (optional) Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors
B609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
B802 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
B803 High-Strength Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors.
B856 Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS).
B958 Extra-High-Strength and Ultra-High-Strength Class A Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors.

Platte/ACSS/TW Conductor Specification

Get all the answers to the most frequently asked questions (FAQs) regarding Platte/ACSS/TW Conductor Specifications,Platte/ACSS/TW Conductor data sheet,Platte/ACSS/TW Conductor size,Platte/ACSS/TW Conductor full form,Platte/ACSS/TW Conductor ampacity,Platte/ACSS/TW Conductor diameter and much, much more technical specification.

Size (kcmil)1569
Type No.5
Cross Sectional Area Aluminum (in²)1.2323
Cross Sectional Area Total (in²)1.2957
Stranding No of Layers of Aluminum3
Stranding No. of Aluminum Wires33
No. & Diameter Individual Steel Wire7 x 0.1074
Diameter Steel Core (in.)0.3222
Diameter Complete Cable (in.)1.334
Alum. Weight (lbs/MFT)1478
Steel Weight (lbs/MFT)215
Total Weight (lbs/MFT)1693
Rated Breaking Strength Standard Strength (lbs)23,100
Rated Breaking Strength High Strength (lbs)24,600
Rated Breaking Strength Ultra High Strength (lbs)27,500
Resistance DC @ 20 °C (ohms/mile)0.0564
Resistance AC @ 75 °C (ohms/mile)0.074
Ampacity @ 75 °C (amps)1319
Ampacity @ 100 °C (amps)1637
Ampacity @ 150 °C (amps)2092
Ampacity @ 200 °C (amps)2439
Ampacity @ 250 °C (amps)2692

*Data provided on this page is subject to change based on different manufacturers variances.

Platte/ACSS/TW Conductor Price

The price of Platte/ACSS/TW Conductor is influenced by various factors such as the market prices of aluminum and steel, manufacturing costs, transportation costs, supply and demand in the market. If you need to get the Platte/ACSS/TW Conductor price per kg, you can directly contact us by email or whatsapp. As a manufacturer of Platte/ACSS/TW Conductor, we will quote a very low price that meets your expectations according to the specifications, length and quantity you need .

Whatsapp Chat Email to us

As a professional Platte/ACSS/TW Conductor manufacturer, JYTOP has over 30 years of production experience and 15 years of export experience.Our acsr dog conductor export such as South Africa, Philippines, Indonesia, Malaysia, Singapore, Vietnam, Korea, Mongolia, Yemen, Cambodia, Thailand, Kenya, Tanzania, UAE, Botswana,Nigeria, Panama, Iran etc.High quality service and production are the first choice of many customers.

HS Code for Platte/ACSS/TW Conductor

The HS code for Platte/ACSS/TW Conductor is 7614100000.
HSN code for Platte/ACSS/TW Conductor in India is 7614100000.

*The HS code is used for customs and trade purposes to identify products and determine duties and taxes on imports and exports.

Following ACSS Conductor Types We Offer:

If you have any questions regarding our services, please contact us or email at [email protected].

Related Products:

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

Request a quote