Schuylkill/ACSS/TW Conductor

ACSS/TW Conductor

1657.4 Schuylkill/ACSS/TW Aluminum Conductor Steel Supported Trapezoidal Shaped Aluminum Strands

Get Latest Price Email to us

Item Value
Schuylkill/ACSS/TW Conductor size 1657.4
Schuylkill/ACSS/TW Conductor Stranding 36/7
Schuylkill/ACSS/TW Conductor weight per km 2,779.9 kg/km
Schuylkill/ACSS/TW Conductor overall diameter 35.2 mm
Schuylkill/ACSS/TW Conductor current carrying capacity @75 °C:1370amps
@100 °C:1702amps
@150 °C:2177amps
@200 °C:2539amps
@250 °C:2805 Amps
Schuylkill/ACSS/TW Conductor resistance and reactance

Learn more about ACSS ACSS/AW ACSS/TW Conductor

Applications

Schuylkill/ACSS/TW Conductor is designed for overhead distribution and transmission lines. ACSS/TW is designed to operate continuously at elevated temperatures up to 250°C without loss of strength, it sags less under emergency electrical loadings than ACSR/TW, excellent self-damping properties, and its final sags are not affected by long-term creep of aluminum.

Also Known As:

Schuylkill/ACSS/TW Conductor,Schuylkill/ACSS/TW Cable,Schuylkill/ACSS/TW Wire,1657.4 Schuylkill/ACSS/TW Conductor,1657.4 Schuylkill/ACSS/TW Cable,1657.4 Schuylkill/ACSS/TW Wire.

Standards:

B500 Metallic Coated Stranded Steel Core for Use in Overhead Electrical Conductors.
B502/B502M (optional) Standard Specification for Aluminum-Clad Steel Core Wire for Use in Overhead Electrical Aluminum Conductors
B609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
B802 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
B803 High-Strength Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors.
B856 Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS).
B958 Extra-High-Strength and Ultra-High-Strength Class A Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors.

Schuylkill/ACSS/TW Conductor Specification

Get all the answers to the most frequently asked questions (FAQs) regarding Schuylkill/ACSS/TW Conductor Specifications,Schuylkill/ACSS/TW Conductor data sheet,Schuylkill/ACSS/TW Conductor size,Schuylkill/ACSS/TW Conductor full form,Schuylkill/ACSS/TW Conductor ampacity,Schuylkill/ACSS/TW Conductor diameter and much, much more technical specification.

Size (kcmil)1657.4
Type No.7
Cross Sectional Area Aluminum (in²)1.302
Cross Sectional Area Total (in²)1.392
Stranding No of Layers of Aluminum3
Stranding No. of Aluminum Wires36
No. & Diameter Individual Steel Wire7 x 0.1280
Diameter Steel Core (in.)0.384
Diameter Complete Cable (in.)1.386
Alum. Weight (lbs/MFT)1563
Steel Weight (lbs/MFT)305
Total Weight (lbs/MFT)1868
Rated Breaking Strength Standard Strength (lbs)29,100
Rated Breaking Strength High Strength (lbs)30,900
Rated Breaking Strength Ultra High Strength (lbs)34,900
Resistance DC @ 20 °C (ohms/mile)0.0533
Resistance AC @ 75 °C (ohms/mile)0.07
Ampacity @ 75 °C (amps)1370
Ampacity @ 100 °C (amps)1702
Ampacity @ 150 °C (amps)2177
Ampacity @ 200 °C (amps)2539
Ampacity @ 250 °C (amps)2805

*Data provided on this page is subject to change based on different manufacturers variances.

Schuylkill/ACSS/TW Conductor Price

The price of Schuylkill/ACSS/TW Conductor is influenced by various factors such as the market prices of aluminum and steel, manufacturing costs, transportation costs, supply and demand in the market. If you need to get the Schuylkill/ACSS/TW Conductor price per kg, you can directly contact us by email or whatsapp. As a manufacturer of Schuylkill/ACSS/TW Conductor, we will quote a very low price that meets your expectations according to the specifications, length and quantity you need .

Whatsapp Chat Email to us

As a professional Schuylkill/ACSS/TW Conductor manufacturer, JYTOP has over 30 years of production experience and 15 years of export experience.Our acsr dog conductor export such as South Africa, Philippines, Indonesia, Malaysia, Singapore, Vietnam, Korea, Mongolia, Yemen, Cambodia, Thailand, Kenya, Tanzania, UAE, Botswana,Nigeria, Panama, Iran etc.High quality service and production are the first choice of many customers.

HS Code for Schuylkill/ACSS/TW Conductor

The HS code for Schuylkill/ACSS/TW Conductor is 7614100000.
HSN code for Schuylkill/ACSS/TW Conductor in India is 7614100000.

*The HS code is used for customs and trade purposes to identify products and determine duties and taxes on imports and exports.

Following ACSS Conductor Types We Offer: